Electrical Specifications
|
Power Consumption |
Sleep Mode |
Primary Battery |
< 27.5 µA @ 7.2VDC (while sampling digital inputs) |
Rechargeable |
< 50 µA @ 3.7 VDC (while sampling digital inputs) |
Active Mode |
Each GPRS transmission |
<1 mAh @ 3.7 VDC |
Power Supplies |
Sensors1 |
Main Power Supply |
3 or 5 VDC @ 200 mA |
Secondary Power Supply |
5 VDC @ 200 mA, 12 Vdc @ 60 mA or 19 Vdc @ 50mA |
Node |
Primary Batteries or External Power Suply |
5-24 VDC2 |
Rechargeable 3 (Li-Ion and Li-polymer) |
Charger Input Voltage |
From 5 to 17 VDC @2A max. |
Voltage Range |
3.4 – 4.2 VDC |
Internal Memory |
4Mbits (> 46.500 data points + time stamp). Other options upon request |
Real Time Clock |
Two independent RTC for time management. Automatic synchronization. |
Operating Temperature Range |
-35 C to +80 C |
Input Channels
|
Analog 4
(12 bits resolution) |
Current |
Range |
4 – 20 mA |
Input impedance |
249 Ohms |
Voltage5 |
0 – 10 VDC |
Digital6 |
Pulse Counter |
Minimum pulse width: 500 us |
Frecuency Meter
(Average) |
0 Hz – 4 kHz ( Hz) |
Frequency Meter
(Instantaneous) |
0 Hz – 4 kHz (±1Hz) |
Open/Close State |
Minimum pulse width: 1 sec |
Physical Specifications
|
Dimensions |
87 x 57 x 36 mm |
Dimensions including external connectors |
100 x 60 x 55 mm |
Weight |
< 150 g |
Material |
ABS Plastic |
Color |
Black RAL 7011 |
Ingress Protection |
IP54 |
Communications
|
Technologies |
Transmission |
Quad-Band GPRS Class 12 |
Configuration |
Micro USB 2.0 |
Antenna 7 |
MCX-Female connector |
Additional Characteristics |
Temperature Sensor |
Resolution |
12 bits |
Accuracy |
± 1 C (from -40 C to 125 C) |
LED Indicators |
For configuration and status assistance. |
GPRS Data Plan |
15 or 100 MB data plans, with private IP and private APN to enhance security.
Included within Kunak®Cloud services. |
Firmware Features
|
Scheduling |
Sampling |
Local and remote scheduling at intervals between 10 seconds and 6 hours. |
Sending |
Uploading period to the cloud from 1 minute to 1 day. |
Configurable Working Mode |
Normal Mode |
The node takes readings every sampling period, stores them and sends them to the cloud every uploading period |
Power Safe Mode8 |
The node takes readings every sampling period, and sends only the average to Kunak®Cloud every uploading period. |
Thresholds and Alarms |
Battery, signal, temperature and any input channel measured have maximum, minimum or asynchronous open/close state configurable thresholds via Kunak®Cloud. If a threshold is exceeded, it immediately triggers an alarm status to the cloud with the data measured since the last sending period (or just the averages in Power Safe Mode) and the overcome value. This feature is available in both the Normal and Power Safe Mode. |
Notifications |
Email notifications are available when configured via Kunak®Cloud.
Smartphone and tablet notifications via Kunak®Watcher. |
Open API |
Secure RESTful WEB SERVICES |
Most of the parameters can be customized. For any specific requirements contact sales@kunak.es
[1] Configurable pre-heating time to reduce power leakage to the sensors. Higher current power supplies options available: 5 V @ 450 mA, 12 V @ 220 mA or 24 V @ 100 mA.
[2] Primary batteries or external power supply up to 42 Vdc is also available under request.
[3] Power path management available. The power path feature allows powering the system from a high efficiency DC to DC converter while simultaneously and independently charging the batteryThis enhances battery life.
[4] Analog input type has to be indicated following the ordering info section.
[5] (-10 – 0), (-10 – +10) and (0 – +5 V) voltage analog input configurations available.
[6] Voltage digital input type also available, for pulse counter, frequencymeter and open/close state applications.
[7] Detachable antenna. Other options under request.
[8] Very useful working mode to reduce power consumption and the amount of data transmitted while maintaining the control over any parameter or event checking the thresholds configured. This operating mode allows configuring higher sending periods and knowing just the average behavior of any parameter, while the thresholds are checked every sampling period for the analog and digital sensors (pulse counters and frequency meters) or when asynchronous open/close state is triggered (at any time).